For disturbance voltage measurements on single-phase EUTs
The R&S ENV216 two-line V-network meets the requirements of CISPR 16-1-2 and EN 55016-1-2 for V-networks with a simulated impedance of (50 μH + 5 Ω) || 50 Ω in the frequency range from 9 kHz to 30 MHz as well as the ANSI C63.4 in the frequency range from 150 kHz to 30 MHz. A socket with protective earth contacts connects to the EUT. Various models with country-specific connector systems are available. The compact design and low weight make the R&S®ENV216 ideal for frequently varying applications, especially for on-site disturbance voltage measurements on single-phase EUT.
Key facts
- Frequency range 9 kHz to 30 MHz
- Power-handling capacity up to 16 A, constant current (country-specifi c)
- Simulated impedance (50 µH + 5 Ω) || 50 Ω in line with CISPR 16-1-2 Amd. 2:2006
- V-network in line with CISPR, EN, VDE, ANSI, FCC Part 15 and MIL-STD-461D, E and F
- Calibrated in line with CISPR 16-1-2
Benefits and key features
Air-core design and artificial hand
The R&S®ENV216 two-line V-network is based on air-core
inductances and contains an artificial hand.
Switch-selectable highpass filter of 150 kHz
To prevent the measuring receiver from being overdriven
by low-frequency spectra of high level, a 150 kHz highpass
filter can be cut in.
Built-in 10 dB attenuator pad
To ensure standard impedance irrespective of the receiver
input attenuation, the R&S®ENV216 is equipped with a
10 dB attenuator pad.
Built-in pulse limiter (can be switched off)
A built-in pulse limiter which can be switched off protects
the receiver input.
Remote control with TTL levels (compatible with
Rohde&Schwarz measuring receivers)
TTL control inputs that can be driven by controllers and
Rohde&Schwarz measuring receivers are provided for
remote control in automatic test systems (phase selection
and activation of highpass filter). Optocouplers prevent
pick-up of external disturbance.